AMT B0x-FxxTII for DIN rail, with RTC and communication, up to 65 A

Three-phase multifunctional static electricity meters AMT B0x-FxxTIIx are determined for measurement of active and reactive electric energy, instantaneous active power for consumption and supply, maximum demand, voltage, current and power factor in threephase four wires networks in diredct or indirect connection. They enable measurement of energy in rates controlled by internal clock (up to 4 rates) or externally controlled in two rates. The measured values stored in registers according to the OBIS codes are displayed on LCD in cyclic or stepping mode. The data are stored in non-volatile memory during power outage. The electricity meters can be parametrized and readout by using optical probe AMOS type and software supplied by the manufacturer. The test pulses indicated by red LED are proportional to the consumed energy.

Properties

  • Meter case width 7M (1M = 18 mm);
  • Intended for indoor mounting on DIN rail (35 mm);
  • Measurement  of energy, power, maximum demand,  voltage, current, power factor ... (A+, A-, R+, R-, P+, P-, Pmax, U, I, cos j...);
  • Historical records of the selected registers, created in the end of month - maximum 15 month historical records (A+, A-, R+, R-, Pmax);
  • Events records (about missing voltage, covers removal, influence of magnetic field...); number of events and the date of their occurrence;
  • Record data profiles;
  • Passive transmitting pulse SO output for remote transmission (separately for active and reactive energy);
  • Communication interface;
  • Complies with IEC/EN 62052-11 + IEC/EN 62053-21; EN 50470-3 and with requirements of European Parliament and EC Directive 2014/32/EU;
  • Supplied initialy verificated for the billing measurement of active energy.

Technical data

Precision class
active energy
A or B (according to MID),
2 or 1(accord. to EN 62053-21)
Precision class
reactive energy
3 or 2
(according to EN 62053-23)
Reference voltage U[V] 33x220/380, 3x230/400, 
3x240/415, (-30,+15%)
Reference current Iref [A]
direct connection
5; 10
Nominal current In [A]
indirect connection
5
Adjustable ratios
(CTR multiplier values)
1, 10, 12, 15, 20, 24, 25, 30, 40, 50, 60, 
80, 100, 120, 150, 160, 200, 240, 250, 
300, 400, 480, 500, 600
Starting current Ist [A]
≤ 0,02 and 0,04 / 0,01
Transient current ltr [A] 
direct/indirect connection
0,5 and 1 / 0,25
Minimal current Imin [A] 
direct/indirect connection
0,25 and 0,5 / 0,05
Maximal current Imax [A] 
direct/indirect connection
65 / 10
Reference frequency [Hz] 50 (±10 %)
Power consumption - Voltage circuit  [VA/W] ≤ 1,6/ 0,8 
Power consumption - Current circuit  [VA] ≤ 0,05
Impulse constatnt for test output kTOA [imp/kWh] 1 000, 5 000
Impulse constatnt for test output kTOR [imp/kvarh] 1 000, 5 000
Impulse constatnt for impulse output  kSOA [imp/kWh] 1000 or 1000/K 
(K = 2 to 10),  5000
Impulse constatnt for impulse output  kSOR [imp/kvarh] 1000 or 1000/K 
(K = 2 to 10),  5000
Transistor output SO 24 V / 30 mA
Operating temperature -40 °C to +70 °C 
Mean temperature coefficient [%/K] ≤ 0,04
Terminals current ; voltage ; auxiliary [mm] ø 6 ; ø 3 ; ø 3 
Degree of protection IP51 
Dimensions [mm] 126 x 105/131 x 59