AMS B1x-OAx for active energy measuring, single-rate and double-rate

Single-phase static electricity meters AMS B1x-OAx are determined for direct and indirect measurement of active energy and displaying values on LCD, with measurement of instantaneous RMS values of voltage, current and P.F. The measured values are stored into special registers marked according to the OBIS codes. In cyclic mode the energy at 1 or 2 rates is displayed, in step mode which is controlled by light pen are displayed also other measured values.

Properties

  • The meters can be mounted on the DIN rail (the clips only on request);
  • Removable and adjustable upper hinge is included in the package;
  • Passive transmitting pulse SO output for remote transmission;
  • Resistant to external influence;
  • Complies with IEC/EN 62052-11, IEC/EN 62053-21; 
  • EN 50470-1, EN 50470-3 and with requirements of European Parliament and EC Directive 2014/32/EU (MID);
  • It is supplied initially verificated for billing measurement.

Technical data

Precision class A or B (according to MID),
2 or 1 (accord. to EN 62053-21)
Reference voltage [V] 120, 220, 230, 240
(-30,+15%)
Reference frequency [Hz] 50 or 60
Reference current Iref[A]
direct connection
5 and 10 
Nominal current In [A]
indirect connection

Transient current Itr [A]
direct/indirect connection
0,5 and 1 / 0,25
Starting current Ist [A]
direct/indirect connection
≤ 0,02 and 0,04 / 0,01
Minimal current Imin [A]
direct/indirect connection
0,25 and 0,5 / 0,05
Maximal current Imax [A]
direct/indirect connection
40, 60, 80 (BS), 100 (BS) / 6; 7,5; 10
Power consumption - voltage circuit  [VA/W] ≤ 7,5 VA/0,4 
Power consumption - current circuit  [VA] ≤ 0,1 
Impulse constant for test output kTO [imp/kWh]
1 – 10 000, normally 5 000
Impulse constant for impulse output kSO [imp/kWh]
1 – 10 000, normally 2 500
Transistor output SO 24 V / 30 mA
Operating temperature  - 40 °C up to + 70 °C
Mean temperature coeff. [%/K] ≤ 0,04 
Terminals current; voltage ; auxiliary [mm] BS (DIN) ø 8 ; ø 3 ; ø 3 (ø 7 ; ø 3 ; ø 3)
Fixing holes distance - w x h [mm] BS (DIN) 104 - 112x115 - 155
(92 - 112x115 - 155)
Meter dimensions - w x h/h´x d [mm] BS (DIN) 130 x 129/190 x 60
(130 x 122/171 x 60)
Weight [kg] ≤ 0,6